Honeywell International Inc. WFSRM Manuale Utente

Pagina di 68
SWIFT™ Smart Wireless Integrated Fire Technology Manual — P/N LS10036-000NF-E:C  5/8/2015
15
Mounting and Wiring
FWSG FlashScan Wireless System Gateway
 
2.7.3  Gateway Powered by the SLC
To power the gateway using the signaling line circuit, connect the gateway as described in the table 
and graphic below:
Figure 2.5  FWSG Mounting Plate - Terminal Layout
A7 - SLC Out+/In+
A6 - SLC In+/Out +
A5 - SLC- (Common)
A4 - SLC Power Select 2
A3 - Power +24VDC
A2 - Power Ground
A1 - SLC Power Select 1
2.4
.w
m
f
Terminal 
Pins
Description 
A5 and A7 SLC - (Common) & SLC Output +
A5 and A6 SLC - (Common) & SLC Input +
A4 and A5 Jumper selection to enable power from the SLC supply. (Insert Jumper when using SLC power.)
A3
Unused
A1 and A2 Jumper selection to enable power from the SLC supply. (Insert Jumper when using SLC power.)