Honeywell International Inc. WFSRM Manuale Utente

Pagina di 68
SWIFT™ Smart Wireless Integrated Fire Technology Manual — P/N LS10036-000NF-E:C  5/8/2015
17
Configuration and Programming
FWSG FlashScan Wireless System Gateway
The gateway provides isolation of short circuits of the SLC in Class A (Style 6) installations. SLC 
connections are power-limited by the panel. +24VDC must be power-limited by the source.
2.8  Configuration and Programming
To successfully configure and/or program the gateway:
1. Create a profile. A profile binds a gateway and the devices in a mesh network together.  The 
profile will contain a mesh ID that is used when forming the associations. All devices, 
including the gateway, require a common profile.
2. Distribute the profile. Distribute the profile to every device that will be a part of the mesh. This 
will enable all the devices that have that profile to form associative links when the mesh is 
formed.
3. Form the mesh. The mesh cannot be formed until the profile is assigned to the gateway and 
distributed to its devices. 
These steps may be performed with or without using SWIFT Tools.
2.8.1  Configuration and Programming Without Using SWIFT Tools
This section explains the configuration of the gateway using only a magnet and a screw driver. For 
configuration instructions using SWIFT Tools, refer to Section 2.8.2. 
There are two ways to provide a gateway with a profile without using SWIFT Tools.
Create a new profile using the gateway.
Assign a previously created profile to the gateway using a distributor.
Create a New Profile
To create a unique profile in the gateway without using SWIFT Tools: 
+
+
-
-
+
-
Figure 2.7  Wiring Connections: FWSG Powered by an External, Regulated +24VDC Source
SLC in from FACP/device
External +24VDC Power
SLC out to next device (Class B)
or SLC return to FACP (Class A)
2.
6
.w
m
f
NOTE: It is recommended to use the same wire gauge if there are multiple connections to the 
same terminal.