SWIFT™ Smart Wireless Integrated Fire Technology Manual — P/N LS10036-000NF-E:C 5/8/2015
FWSG FlashScan Wireless System Gateway
Mounting and Wiring
    
The gateway provides isolation of short circuits on the SLC in Class A (Style 6) installations. SLC 
connections are power-limited by the panel. An interruption in the SLC that causes a loss of power 
at the gateway for more than 100ms may result in a trouble condition and loss of fire protection 
provided by the wireless devices for approximately 15 minutes. Use of an external +24V power 
source (not SLC power) is recommended for installations that require fire protection in the pres-
ence of short circuits, including Class A applications and applications that use isolator modules. 
Refer to the SLC Wiring Manual for more information on wiring using isolators.
2.7.4  Gateway Powered by an External, Regulated +24VDC Source
To power the gateway using an external, regulated +24VDC source, connect the gateway as 
described in the table and drawing below.
+
+
-
-
Figure 2.6  Wiring Connections: FWSG Powered by the SLC
SLC out to next device (Class B)
or SLC return to FACP (Class A)
SLC in from FACP/device
jumpers
2.
5.w
m
f
NOTE: Use of the same wire gauge is recommended if there are multiple connections to the 
same terminal.
Terminal Pins
Devices Powered
A5 & A7
SLC Output
A5 & A6
SLC Input
A4
Unused
A2 & A3
+24VDC input. Voltage range from +18VDC to +30VDC.
Use only power-limited device circuits.
A1
Unused