SWIFT™ Smart Wireless Integrated Fire Technology Manual — P/N LS10036-000NF-E:C 5/8/2015
FWSG FlashScan Wireless System Gateway
Operations
2.9.9  Trouble Messages
NFS2-3030
NCA-2
Onyxworks
NFS2-640
NFS-320
Type
Description
Course of Action
RADIO JAMMING
JAM
Non-latching
The gateway is being 
overloaded with RF energy 
and is unable to receive 
messages from other 
devices. 
Identify any RF emitters in close proximity 
of the gateway and remove them or 
relocate the gateway.
INCOMPAT SOFT
IN SFT
Non-latching
Software mismatch 
between the application 
code for the RF processor 
and the SLC processor.
Use SWIFT Tools to identify the mismatch, 
and update the processors as necessary 
for compatibility.
MESH IS 
FORMING
MS FRM
Non-latching
The gateway and attached 
devices are searching for 
additional devices to join 
the mesh. The wireless 
system is not able to 
provide fire protection 
during this time.
Wait until all desired wireless devices are 
communicating and are members of the 
mesh network. Once all desired devices 
are in the mesh network, the mesh forming 
mode can be terminated by the user by 
activating the Mesh formation magnetic 
sensor or by using the SWIFT Tools. If no 
action is taken, this mode will 
automatically exit 10 minutes after the last 
device joins.
MESH NOT 
FORMED
NOMESH
Non-latching
The gateway contains a 
profile but has not formed a 
mesh.
RESTRUCTURING RSTRCT
Non-latching
The gateway is performing 
the initial identification and 
assignment of optimal 
communication paths for 
the mesh network.  The 
wireless system is not able 
to provide fire protection 
during this time.
No action needed. The duration of this 
event correlates to the number of devices 
in the mesh. A fully loaded mesh may take 
up to 5 minutes to restructure.
PROFILE MISSING PR MIS
Non-latching
The gateway is in the 
factory default state and is 
not providing fire 
protection.
A profile needs to be created or assigned 
to the gateway before a mesh can be 
formed.
NO WIRELESS  
DEVS
NO DEV
Non-latching
The gateway is functional  
but is not in communication 
with any wireless devices.
Verify the desired wireless devices are in 
range, have matching profiles assigned, 
have fresh batteries, and are not in the 
tampered condition. Initiate “Mesh 
Formation mode” to actively search for 
devices.
ADDRESS FAULT
ADRFLT
Non-latching
There is either a device in 
the mesh set to address 0 
or there is a duplicate 
address used for another 
wireless module at the 
address of the gateway.
The offending device (detector or module 
set at address 0 or module at the same 
address as the gateway) will be indicating 
the LED pattern for address fault. Find and 
resolve that device.
MAX  GATEWAYS
MAX GW
Non-latching
Wireless communication 
reliability is compromised 
due to the installation limits 
of Notifier wireless systems 
being exceeded.
Investigate for overlapping or adjacent 
wireless systems produced by Notifier.  
Reduce the instances of overlap by 
removing systems, or devices in the 
overlapping region.  Refer to Section 2.9.7 
on the installation limits for the Notifier 
wireless system. 
Table 2.1  Trouble Messages