Honeywell International Inc. WFSRM Manuale Utente
30
SWIFT™ Smart Wireless Integrated Fire Technology Manual — P/N LS10036-000NF-E:C 5/8/2015
FWSG FlashScan Wireless System Gateway
Operations
2.9.9 Trouble Messages
NFS2-3030
NCA-2
Onyxworks
NFS2-640
NFS-320
Type
Description
Course of Action
RADIO JAMMING
JAM
Non-latching
The gateway is being
overloaded with RF energy
and is unable to receive
messages from other
devices.
overloaded with RF energy
and is unable to receive
messages from other
devices.
Identify any RF emitters in close proximity
of the gateway and remove them or
relocate the gateway.
of the gateway and remove them or
relocate the gateway.
INCOMPAT SOFT
IN SFT
Non-latching
Software mismatch
between the application
code for the RF processor
and the SLC processor.
between the application
code for the RF processor
and the SLC processor.
Use SWIFT Tools to identify the mismatch,
and update the processors as necessary
for compatibility.
and update the processors as necessary
for compatibility.
MESH IS
FORMING
FORMING
MS FRM
Non-latching
The gateway and attached
devices are searching for
additional devices to join
the mesh. The wireless
system is not able to
provide fire protection
during this time.
devices are searching for
additional devices to join
the mesh. The wireless
system is not able to
provide fire protection
during this time.
Wait until all desired wireless devices are
communicating and are members of the
mesh network. Once all desired devices
are in the mesh network, the mesh forming
mode can be terminated by the user by
activating the Mesh formation magnetic
sensor or by using the SWIFT Tools. If no
action is taken, this mode will
automatically exit 10 minutes after the last
device joins.
communicating and are members of the
mesh network. Once all desired devices
are in the mesh network, the mesh forming
mode can be terminated by the user by
activating the Mesh formation magnetic
sensor or by using the SWIFT Tools. If no
action is taken, this mode will
automatically exit 10 minutes after the last
device joins.
MESH NOT
FORMED
FORMED
NOMESH
Non-latching
The gateway contains a
profile but has not formed a
mesh.
profile but has not formed a
mesh.
RESTRUCTURING RSTRCT
Non-latching
The gateway is performing
the initial identification and
assignment of optimal
communication paths for
the mesh network. The
wireless system is not able
to provide fire protection
during this time.
the initial identification and
assignment of optimal
communication paths for
the mesh network. The
wireless system is not able
to provide fire protection
during this time.
No action needed. The duration of this
event correlates to the number of devices
in the mesh. A fully loaded mesh may take
up to 5 minutes to restructure.
event correlates to the number of devices
in the mesh. A fully loaded mesh may take
up to 5 minutes to restructure.
PROFILE MISSING PR MIS
Non-latching
The gateway is in the
factory default state and is
not providing fire
protection.
factory default state and is
not providing fire
protection.
A profile needs to be created or assigned
to the gateway before a mesh can be
formed.
to the gateway before a mesh can be
formed.
NO WIRELESS
DEVS
DEVS
NO DEV
Non-latching
The gateway is functional
but is not in communication
with any wireless devices.
but is not in communication
with any wireless devices.
Verify the desired wireless devices are in
range, have matching profiles assigned,
have fresh batteries, and are not in the
tampered condition. Initiate “Mesh
Formation mode” to actively search for
devices.
range, have matching profiles assigned,
have fresh batteries, and are not in the
tampered condition. Initiate “Mesh
Formation mode” to actively search for
devices.
ADDRESS FAULT
ADRFLT
Non-latching
There is either a device in
the mesh set to address 0
or there is a duplicate
address used for another
wireless module at the
address of the gateway.
the mesh set to address 0
or there is a duplicate
address used for another
wireless module at the
address of the gateway.
The offending device (detector or module
set at address 0 or module at the same
address as the gateway) will be indicating
the LED pattern for address fault. Find and
resolve that device.
set at address 0 or module at the same
address as the gateway) will be indicating
the LED pattern for address fault. Find and
resolve that device.
MAX GATEWAYS
MAX GW
Non-latching
Wireless communication
reliability is compromised
due to the installation limits
of Notifier wireless systems
being exceeded.
reliability is compromised
due to the installation limits
of Notifier wireless systems
being exceeded.
Investigate for overlapping or adjacent
wireless systems produced by Notifier.
Reduce the instances of overlap by
removing systems, or devices in the
overlapping region. Refer to Section 2.9.7
on the installation limits for the Notifier
wireless system.
wireless systems produced by Notifier.
Reduce the instances of overlap by
removing systems, or devices in the
overlapping region. Refer to Section 2.9.7
on the installation limits for the Notifier
wireless system.
Table 2.1 Trouble Messages