Operations
WSK-WGI Wireless System Gateway
Activating the Profile Magnetic Sensor
Activating the profile magnetic sensor (refer to Figure 2.2) when the gateway has a profile will put the gateway in a mode of distributing
the profile to any device that requests a profile. The gateway’s LED pattern will be altered when it is distributing a profile for easy iden-
tification. Profile distribution will automatically terminate after 10 minutes. For more information on gateway LED patterns, refer to
the profile to any device that requests a profile. The gateway’s LED pattern will be altered when it is distributing a profile for easy iden-
tification. Profile distribution will automatically terminate after 10 minutes. For more information on gateway LED patterns, refer to
2.8.4 SLC Configuration
The gateway:
communicates with the control panel via the SLC.
is only compatible with Gateway firmware version 2.1 or higher.
occupies one module SLC address. Set the address using the rotary dials on the gateway prior to installation.
The SLC point uses the following configuration parameters:
•
•
Module Type: Monitor
•
Type Code Label: RF GATEWAY
•
FlashScan Type: RF GATEWAY
A gateway does not initiate alarms but the point is used for event reporting.
2.9 Operations
2.9.1 Modes of Operation
Start-up Mode
Start-up mode is a temporary mode of operation. During start-up mode a profile can be created or removed. The start-up period lasts for
10 seconds. If a particular unit contains a profile, the LEDs double blink yellow every second. If the unit does not contain a profile, the
LEDs double blink red every second.
During start-up, the gateway does not provide fire protection nor does it respond to the FACP.
After start-up, the gateway proceeds to the factory default mode if no profile exists. In the presence of a profile, the gateway will pro-
ceed to mesh formation mode if it was previously part of a mesh network or normal mode if it was not previously part of a mesh net-
work.
LEDs double blink red every second.
During start-up, the gateway does not provide fire protection nor does it respond to the FACP.
After start-up, the gateway proceeds to the factory default mode if no profile exists. In the presence of a profile, the gateway will pro-
ceed to mesh formation mode if it was previously part of a mesh network or normal mode if it was not previously part of a mesh net-
work.
TENS
8 9
10
11
12
13
14
15
0
1
2
3
4
5
6 7
ONES
8 9
0
1
2
3
4
5
6 7
Figure 2.14 Address Rotary Switches
S
L
C-se
ta
d
dtp
h.wmf
NOTE: When a wireless relay, wireless AV base, or wireless sync module is in use, module device count must be limited to 109 modules
per loop. This includes wired and wireless modules that are on the same loop. The module address range must be within 1-109.
Figure 2.15 Gateway Modes Of Operation
Start-up
Factory
Default
Profile
Configured
Mesh
Formation
Initial Mesh
Restructuring
Normal Mode
Mesh
Restructuring
Rescue Mode
Fire Protection Provided
Neighboring
Network Scan
Mesh
Upgrade in
Progress
Mesh
Upgrade
Preparation