SWIFT® Smart Wireless Integrated Fire Technology Manual — P/N LS10036-000SK-E:B  11/9/2017
11
Magnet Sensors
WSK-WGI Wireless System Gateway
2.3.1  Environmental Specifications
2.4  Magnet Sensors
2.4.1  Profile Magnetic Sensor
The profile magnetic sensor (refer to Figure 2.2) is used to create a unique profile upon start-up. It can also be used to start profile distri-
bution for a gateway that contains a profile. The LED next to the profile magnet sensor turns on green for ½ a second when the sensor is 
activated.
2.4.2  Mesh Formation Magnetic Sensor
The mesh formation magnetic sensor (refer to Figure 2.2) transitions the gateway in and out of mesh formation mode. The initial activa-
tion of the sensor puts the gateway in mesh formation mode (as long as it contains a profile). A subsequent activation of the magnetic 
sensor transitions the gateway out of mesh formation and into the initial mesh restructuring and normal mode. The gateway can be 
placed back into mesh formation mode by activating the magnet sensor once again. The LED next to the profile magnet sensor turns on 
green for ½ a second when the sensor is activated.
The Mesh formation magnetic sensor can also be used to create a profile on start-up for a gateway that does not already contain a profile.
2.5  LED Indicators
The two LEDs on the gateway blink in the same pattern to allow the LED to be viewed from any angle. LED patterns are explained in 
2.6  Installing the Gateway
2.6.1  Before Installing
Choose a location for the gateway that is clean, dry, and vibration-free. The area should be readily accessible with sufficient room to eas-
ily install and maintain the gateway. Metal obstructions impede the radio frequency communication and should be avoided. Carefully 
unpack the system and inspect for shipping damage if any. All wiring must comply with the national and local codes for fire alarm sys-
tems. 
Minimum signal strength level needed at the receiver for a secondary path or 
primary path with weak link trouble reporting disabled.
Must be 18 dBm higher than the noise 
floor down to a minimum of -80dBm
1
Maximum ambient noise level
-85dBm
Maximum RF Power Output
+17dBm (Tx power level without antenna)
Radio Frequency
Lower ISM Band (902 - 928MHz).
1
Ensure that the primary path signal strength level is within recommended guidelines to assure proper communication in the 
mesh network.
System
Operating Temperature
StorageTemperature
Humidity
Gateway
0°C-49°C / 32°F-120°F
-10°C- 60°C / 14°F-140°F
10 to 93% RH, Non-condensing
Figure 2.2  LEDs and Magnetic Sensors on the WSK-WGI
LEDs
Mesh 
Formation 
Magnetic 
Sensor
Profile 
Magnetic 
Sensor