Honeywell International Inc. WFSSM Manuale Utente

Pagina di 64
SWIFT® Smart Wireless Integrated Fire Technology Manual — P/N LS10036-000SK-E:B  11/9/2017
21
Operations
WSK-WGI Wireless System Gateway
Bootloader Mode
The gateway enters the bootloader mode when its firmware is being updated using SWIFT Tools. The gateway does not communicate 
with the FACP during bootloader mode. The gateway reports “Bootloader” to the communicator display of the SWIFT Tools application.
Mesh Upgrade
Starting with version 3.0, firmware updates for the wireless mesh devices (detectors, monitor module, relay, etc.) can be broadcast over 
the mesh network. Fire protection will not be provided during the upgrade process. 
SWIFT tools will be used to initiate and monitor the upgrade process. During the upgrade process each device in the mesh will appear as 
a no answer or invalid reply. Refer to Section 2.9.10 for more information on the mesh upgrade process.
Neighboring Network Scan
A Mesh network will identify adjacent mesh networks for the purpose of avoiding communication collisions and for time synchroniza-
tion to ensure end-to-end latency compliance. Fire protection will be provided during a neighboring network scan by all devices that are 
participating in the mesh communication. The gateway reports “Neighboring Scan” to the communicator display of the SWIFT Tools 
application. 
2.9.2  LED Patterns
The LED indicator patterns are provided in Appendix D on page 55.
2.9.3  Lock/Unlock the Gateway
The gateway can be locked to prevent access to the magnetic sensors and to password-protect all wireless interactions. The lock function 
can be performed by SWIFT Tools. When SWIFT Tools is used to lock the gateway, a password must be provided for all future interac-
tions, including unlocking the gateway. If the gateway was previously locked with a password from SWIFT Tools, the previous pass-
word will be applied. Use this password for all future interactions with the SWIFT Tools application. 
Lock/Unlock the Gateway Using SWIFT Tools
To lock/unlock the gateway:
1.
Connect the W-USB adapter to your computer. For more information on USB adapter, refer to Section 5.
2.
Launch the SWIFT Tools application. Refer to Appendix A, “SWIFT Tools” for more information.
3.
From the Home Screen, select the Site SurveyCreate Mesh Network, or Diagnostics function.
4.
Click Operations. The following screen is displayed. 
5.
Select Gateway Operations to lock/unlock the gateway. The Lock/Unlock gateway screen appears, displaying the gateway that is 
locked. 
6.
Select desired gateway and click Lock or Unlock as required.
• Lock - The Lock Gateway screen is displayed. Create a password and click Lock. The gateway is locked.
• Unlock - The Enter password for Gateway screen is displayed. Enter the password and click Unlock. The gateway is 
unlocked.
Figure 2.16  Operations Menu
loc
k_
un
lc
o
k_g
at
e
w
ay
.p
ng
Figure 2.17  Lock/Unlock Screen