Honeywell International Inc. WFSSM Manuale Utente

Pagina di 64
SWIFT® Smart Wireless Integrated Fire Technology Manual — P/N LS10036-000SK-E:B  11/9/2017
29
Section 3: Wireless Devices
3.1  Description
The SWIFT Network consists of the following devices:
WSK-PHOTO - Wireless Photoelectric Smoke Detector  
 -FCC ID: AUBWFSSD
The wireless photoelectric smoke detector is powered by four CR123A batteries. It has a sensor head to detect smoke and LEDs to indi-
cate the activation and trouble status. 
WSK-PHOTO-T - Wireless Photo/Heat Detector  
FCC ID: AUBWFSSD
The wireless photo/heat detector is powered by four CR123A batteries. It has a sensor head to detect heat and LEDs to indicate activa-
tion and trouble status.
WSK-HEAT-ROR - Wireless Rate of Rise Heat Detector  
FCC ID: AUBWFSSD
The rate of rise heat detectors are powered by four CR123A batteries. The detectors have LEDs to indicate the activation and trouble sta-
tus.
WSK-HEAT - Wireless 135° Fixed Heat Detector  
FCC ID: AUBWFSSD
The fixed heat detectors are powered by four CR123A batteries. The detectors have LEDs to indicate the activation and trouble status. 
WSK-MONITOR - Wireless Addressable Monitor Module  
FCC ID: AUBWFSMM
The wireless monitor module is powered by four CR123A batteries. It can be connected to a switch within three feet of its location or 
wired directly to the pull station. The module has LEDs to indicate the activation and trouble status. 
WSK-RELAY - Wireless Addressable Relay Module  
FCC ID: AUBWFSRM 
The wireless relay module is powered by four CR123A batteries
It provides the system with a dry-contact output for activating a variety 
of auxiliary devices, such as fans, dampers, control equipment, etc. Addressability allows the dry contact to be activated, either manually 
or through panel programming, on a select basis. The module has an LED to indicate the activation and trouble status.
WSK-PULL-DA - Wireless Addressable Pull Station  
FCC ID: xxxxx
The wireless pull station is powered by four CR123A batteries. The module has an LED to indicate the activation and trouble status.
The pull station will occupy one module address.
Type Code Label: Monitor
FlashScan Type: RF MONITOR
WAV-RL, WAV-WL, WAV-CRL, WAV-CWL - Wireless Addressable AV bases  
FCC ID: xxxx
The wireless AV base is powered by eight CR123A batteries. Four of the CR123A batteries are used to power the notification element 
and four of the CR123A batteries are used to power the radio communication element. The module has an LED to indicate the activation 
and trouble status. The module requires a non-compact wall or ceiling System Sensor L-series notification device (ordered separately). A 
notification device with an audible component must be set to a non-coded setting (i.e. continuous or Temp3).
The base address set by the code wheels on the AV base will require the following configuration:
Type Code Label: Relay
FlashScan Type: RF RELAY
Base+1 address will use the following configuration:
Type Code Label: Control
FlashScan Type: Control
Wireless related trouble events described in Section 3.6.3 will be indicated at the base address. Open circuit at the base+1 address will 
indicate a missing notification device. Short circuit at the base+1 address will indicate a incorrectly configured or faulted notification 
device.
Both module points will be used to drive the output of the AV unit to the desired pattern below:    
W-SYNC - Wireless Addressable Sync Module  
FCC ID: xxxx
The wireless sync module is 24VDC externally powered and requires 4 supplemental CR123A batteries. The module has an LED to 
indicate the activation and trouble status. The wireless sync module will occupy two consecutive SLC module addresses. 
Base address set by the code wheels on the sync module will use:
Type Code Label: Relay
FlashScan Type: RF RELAY
Base Address
Base+1 Address
Notification Pattern
OFF
OFF
Off
ON
OFF
Strobe Only (Audible Silenced)
ON
ON
Strobe & Audible active
OFF
ON
Magnet Test mode (Strobe & audible activate when magnet is placed on the unit)
NOTE: To configure an audible/visual unit to silence only the audible component with a signal silence command, configure both addresses 
to activate for the alarm condition, the base address shall be non-silenceable and the base+1 shall be silenceable with the appropriate 
resound settings.