Configuration and Programming
Wireless Devices
3.5  Configuration and Programming
Device configuration starts with assigning a profile.
3.5.1  Assigning Profiles
To assign a profile, the device must be in a factory default state. A single red light flashes on the LED confirming that the device is in the 
default state. To restore the device to factory default state, refer to Section 3.5.4, “Restoring a Device to Factory Default”.
There are two methods to assigning a profile.
Assigning a Profile to a Device (Detector or Module) Using a Gateway or Distributor
A gateway that has a profile can be used to distribute that profile to other devices. The gateway must be in distributor mode before it can 
distribute a profile. For more information on converting a gateway to a distributor, refer to Section 2.8.3. A device with a profile can be 
used to distribute the profile. To put a device into distributor mode, refer to topic, “Converting a Device into a Distributor” on page 33.
Distribute a Profile from a Gateway/Distributor to a Detector
To transfer a profile from a gateway/distributor to a detector:
1.
Bring the detector within 20 feet of the gateway/distributor. 
2.
Insert one or more batteries to power on the detector. Ensure the detector is in factory default state. The LED on the detector will 
single-blink or double-blink red confirming that it is in the factory default state. 
3.
Activate the magnet test switch shown in the figure below. (The base with the integral tamper magnet or another magnet can be 
used to do this.) Once the magnet sensor has been activated, the LED blinks red every half second indicating that it is requesting a 
profile. If the profile is successfully received, the green LED turns on steady for 10 seconds. If the profile is not received within 1 
minute, the LED blinks red every ten seconds indicating that it has stopped requesting a profile.     
   Distribute a Profile from a Gateway/Distributor to a Module
To transfer a profile from a gateway/distributor to a module:
1.
Bring the module within 20 feet of the gateway/distributor. 
2.
Insert one or more batteries to power on the module. Ensure the module is in factory default state. If the module is in factory default 
state, the LED blinks red once.
3.
Toggle the state of the tamper condition to instruct the module to request a profile. To toggle the tamper condition state, start with 
the faceplate (with integral magnet) removed.
4.
Quickly replace then remove the faceplate from the module to momentarily activate the magnetic tamper sensor on the module. Do 
not attach the mounting screws for the faceplate during this step. The LED blinks red every half second indicating that it is 
requesting a profile. The green LEDs turn on steady for ten seconds indicating that the profile has been assigned. If the profile is not 
received within 1 minute, the LED blinks red every ten seconds indicating that it has stopped requesting a profile. 
Figure 3.1  Magnetic Sensor on a Detector
ma
gn
etd
e
t.w
m
f
LED
LED
Magnet test 
switch
Tamper 
magnet