Honeywell International Inc. WFSSM Manuale Utente

Pagina di 64
30
SWIFT® Smart Wireless Integrated Fire Technology Manual — P/N LS10036-000SK-E:B  11/9/2017
Wireless Devices
Agency Approvals
Base+1 address will use:
Type Code Label: Control
FlashScan Type: Control
Wireless related trouble events described in Section 3.6.3 will be indicated at the base address.
The end of line supervision of the monitor input and the power monitoring of the external 24VDC supply will be indicated at the base+1 
address. 
The following table indicates the output state. 
    
For more information on the LED indicators, refer to Section 3.6.2.
3.2  Agency Approvals
3.2.1  FCC
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: 
1.
This device may not cause harmful interference. 
2.
This device must accept any interference received, including interference that may cause undesired operation.
3.2.2  Federal Institute of Telecommunications
This device utilizes the Honeywell915 rev A radio module and complies with IFETEL standard(s).
IFT: RCPHOSW14-1983
3.3  Specifications
The following are the specifications for the wireless devices.
3.4  Installing, Mounting, and Wiring Devices
For information on installing the wireless devices, refer to the documents referenced in Section 1.3 on page 8.
Base Address
Base+1 Address
Control Output Signal
Synchronization Output Signal
OFF
OFF
Low (inactive)
Low (inactive)
ON
OFF
High (active)
Strobe Only (Audible Silenced)
ON
ON
High (active)
Strobe & Audible active
OFF
ON
High (active)
Magnet Test mode
NOTE:
1. To configure a NAC circuit, with audible and visual units, to silence only the audible component with a signal silence command, configure 
both addresses to activate for the alarm condition. The base address shall be non-silenceable and the base+1 shall be silenceable with the 
appropriate resound settings.
2. When the sync module is being used for delivering only the synchronization signal (i.e. applications with the MDL3), it is recommended to 
leave the base address point constantly active to eliminate any delay in initial synchronization.
NOTE: When a wireless relay, wireless AV base, or wireless sync module is in use, module device count must be limited to 109 modules 
per loop. This includes wired and wireless modules that are on the same loop. The module address range must be within 1-109.
!
WARNING: DO NOT MAKE CHANGES TO THE EQUIPMENT.
CHANGES OR MODIFICATIONS NOT EXPRESSLY APPROVED BY THE MANUFACTURER COULD VOID THE USER’S 
AUTHORITY TO OPERATE THE EQUIPMENT.
Specification
Data
Radio Frequency
Lower ISM Band (902-928 MHz)
Maximum power output
+17dBm
Minimum signal strength level needed at the receiver for a primary path 
with weak link trouble reporting enabled.
-55dBm
Minimum signal strength level needed at the receiver for a secondary 
path or primary path with weak link trouble reporting disabled.
Must be 18 dBm higher than the noise floor down to -80dBm
Maximum ambient noise level
-85dBm
Minimum battery life
2 years (where the activation of a wireless device is used for 
fire purposes only)
Table 3.1  Wireless Device Specifications