Beha Amprobe GT-800 STD KITVDE-tester 4472062 Manuale Utente

Codici prodotto
4472062
Pagina di 76
GT-600/GT-800 Instruction Manual 
68 
 
 
Protective Bonding Resistance - 5A (R
PE
) 
Measurement range 
0.10 ... 10.00 
 
Display range 
0.00 ... 11.00 
 
Resolution 0.01 
 
Accuracy 
± (5% rdg. + 3 digits) 
Operational error 
± 13% 
Limit value 
  Adjustable 0.01 ... 11.00 
, calculation (by  
 
  length and cross section) available 
Test current 
>5.0 A AC (at mains voltage 230 V, standard  
 
test lead 1.5 m / 0.75 mm
2
 and external  
 resistance 
of 
0.1 
) 
Short-circuit test current 
Approx. 6 A AC (at mains voltage 230 V)  
Open-circuit test voltage 
Approx. 6 V AC, SELV (floating output) 
Test lead compensation 
Up to 5.00 
 by using the COMP key 
Protection against ext. voltage  Fuse F3, blown fuse automatically detected 
AUTO test mode 
  Yes, automatic start and save after connecting 
 
  to PE of DUT 
Pre-Tests and Protection,  
Functions and Messages 
Refer to page 64 
 
Protective Bonding Resistance - 0.2A (R
PE
Measurement range 
0.10 ... 10.00 
 
Display range 
0.00 ... 11.00 
 
Resolution 0.01 
 
Accuracy 
± (5% rdg. + 3 digits) 
Operational error 
± 13% 
Limit value 
  Adjustable 0.01 ... 11.00 
, calculation available 
Test current 
> 0.2 A AC 
Short-circuit test current 
Approx. 0.45 A AC (at mains voltage 230 V)  
Open-circuit test voltage 
Approx. 6 V AC, SELV (floating output) 
Test lead compensation 
Up to 5.00 
 by using the COMP key 
Protection against ext. voltage   Fuse F3, blown fuse automatically detected 
AUTO test mode 
  Yes, automatic start and save after connecting 
 
  to PE of DUT 
Pre-Tests and Protection,  
Functions and Messages 
Refer to page 64 
 
Insulation Resistance (R
ISO
Available protection classes 
Class I with heater, I, II and III 
Measurement terminals class I 
L/N against (PE on test socket in parallel with 
 PROBE 
2) 
Measurement terminals class II  L/N against PROBE 2 
Measurement terminals class III  PROBE 1 against PROBE 2 
Measurement range class I, II 
0.10 ... 10.0 M
 
Measurement range class III 
0.10 ... 5.0 M
 
Display range class I, II 
0.00 ... 9.99 M
, 10.0 ... 49.9 M, 50 ... 100 M 
Display range class III 
0.00 ... 9.99 M
, 10.0 ... 20.0 M 
Resolution 0.01 
M
, 0.1 M, 1 M