Testboy TV 455VDE-tester Testboy TV 455 Manuale Utente

Codici prodotto
Testboy TV 455
Pagina di 76
TESTBOY TV 450 
Resistance of earth connection 
 
32 
5.3 
Resistance of earth connection and equipotential 
bonding 
 
The resistance measurement is performed in order to ensure that the protective 
measures against electric shock through earth connections and bondings are effective. 
Two sub-functions are available: 
 
‰
 
R LOWΩ - Earth bond resistance measurement according to EN 61557-4 (200 
mA), 
‰
 
CONTINUITY - Continuous resistance measurement performed with 7 mA 
(model TESTBOY TV 450 (TYPE B)). 
 
 
See chapter 4.1 Function selection for instructions on 
key functionality. 
Figure 5.8: 200 mA RLOW Ω 
Test parameters for resistance measurement 
 
* model TESTBOY TV 450 (TYPE B) 
TEST Resistance 
measurement sub-function [R LOWΩ, CONTINUITY*] 
Limit 
Maximum resistance [OFF, 0.1 
Ω ÷ 20.0 Ω]