TESTBOY TV 450 
Resistance of earth connection 
 
33 
 
5.3.1 R LOWΩ, 200 mA resistance measurement 
 
The resistance measurement is performed with automatic polarity reversal of the test 
voltage.  
 
Test circuit for R LOWΩ measurement 
 
 
Figure 5.9: Connection of 3-wire test lead plus optional extension lead 
 
Resistance to earth connection and equipotential bonding measurement procedure 
* model TESTBOY TV 450 (TYPE B) 
‰
 
Select continuity function using the function selector switch. 
‰
 
Set sub-function to R LOWΩ
‰
 
Enable and set limit (optional). 
‰
 
Connect test cable to the the instrument. 
‰
 
Compensate the test leads resistance (if necessary, see section 5.3.3). 
‰
 
Disconnect from mains supply and discharge installation to be tested. 
‰
 
Connect the test leads to the appropriate PE wiring (see figure 5.9). 
‰
 
Press the TEST key to perform the measurement. 
‰
 
After the measurement is finished store the result by pressing the MEM button 
(optional)*. 
 
 
Figure 5.10: Example of RLOW result 
Displayed result:  
R................R LOWΩ resistance. 
R+..............Result at positive polarity 
R-...............Result at negative test polarity