TESTBOY TV 450 
Fault loop impedance 
 
44 
Fault loop impedance measurement procedure 
 
* model TESTBOY TV 450 (TYPE B) 
‰
 
Select the 
Zloop 
or 
Zs rcd 
subfunction using the function selector switch and 
¿
/À keys 
‰
 
Select test parameters (optional). 
‰
 
Connect test cable the TESTBOY TV 450. 
‰
 
Connect test leads to the the item to be tested (see 
figure 5.24 and 5.17). 
‰
 
Press the TEST key to perform the measurement. 
‰
 
Store the result by pressing the MEM key (optional)*. 
 
 
Figure 5.25: Examples of loop impedance measurement result 
Displayed results: 
Z..............Fault loop impedance, 
I
SC
............Prospective fault current, 
Lim ..........Low limit prospective short-circuit current value or high limit fault loop 
impedance value for the UK version.  
 
Prospective fault current I
SC
 is calculated from measured impedance as follows: 
 
Z
k
Un
I
SC
SC
×
=
 
where: 
Un ........Nominal U
L-PE
 voltage (see table below), 
ksc .......Correction factor for Isc (see chapter 
4.2.6). 
 
U
n
 
Input voltage (L-PE) 
115 V  (100 V 
≤ U
L-PE
 
< 160 V) 
230 V  (160 V 
≤ U
L-PE
 
≤ 264 V) 
Notes: 
‰
 
High fluctuations of mains voltage can influence the measurement results (the 
noise sign 
 is displayed in the message field). In this case it is recommended 
to repeat few measurements to check if the readings are stable. 
‰
 
This measurement will trip-out the RCD in RCD-protected electrical installation if 
test Zloop is selected. 
‰
 
Select Zs 
rcd
 to prevent trip-out of RCD in RCD protected installation.