Testboy TV 455VDE-tester Testboy TV 455 Manuale Utente

Codici prodotto
Testboy TV 455
Pagina di 76
TESTBOY TV 450 
Earth resistance 
 
46 
 
 
Line to neutral 
Line to line 
Figure 5.28: Examples of line impedance measurement result 
Displayed results: 
Z..............Line impedance, 
I
SC
............Prospective short-circuit current, 
Lim ..........Low limit prospective short-circuit current value or high limit line 
impedance value for the UK version
.
 
 
Prospective short circuit current is calculated as follows: 
 
Z
k
Un
I
SC
SC
×
=
 
where: 
Un ........Nominal L-N or L1-L2 voltage (see table below), 
ksc .......Correction factor for Isc (see chapter 
4.2.6). 
 
U
n
  Input voltage range (L-N or L1-L2)
115 V 
(100 V 
≤ U
L-N
 
< 160 V) 
230 V 
(160 V 
≤ U
L-N
 
≤ 264 V) 
400 V 
(264 V 
< U
L-N
 
≤ 440 V) 
Note: 
 
‰
 
High fluctuations of mains voltage can influence the measurement results (the 
noise sign 
 is displayed in the message field). In this case it is recommended 
to repeat few measurements to check if the readings are stable.