Testboy TV 455VDE-tester Testboy TV 455 Manuale Utente

Codici prodotto
Testboy TV 455
Pagina di 76
TESTBOY TV 450 
Technical specification 
 
64 
0.2
×I
ΔN
 
÷ 2.2×I
ΔN
 (A type, I
ΔN
 <30 mA) 
0.05
×I
ΔN
 
±0.1×I
ΔN
 
0.2
×I
ΔN
 
÷ 2.2×I
ΔN
 (B type)* 
0.05
×I
ΔN
 
±0.1×I
ΔN
 
 
Trip-out time 
Measuring range (ms) 
Resolution (ms) 
Accuracy 
÷ 300 
±3 ms 
 
Contact voltage 
Measuring range (V) 
Resolution (V) 
Accuracy 
0.0 
÷ 19.9 
0.1 
(-0 % / +15 %) of reading 
± 10 digits 
20.0 
÷ 99.9 
0.1 
(-0 % / +15 %) of reading 
The accuracy is valid if mains voltage is stabile during the measurement and PE 
terminal is free of interfering voltages. 
Trip-out measurement is not available for I
ΔN
=1000 mA (RCD type B)*. 
Specified accuracy is valid for complete operating range. 
 
9.4  Fault loop impedance and prospective fault current 
 
9.4.1 No disconnecting device or FUSE selected 
 
Fault loop impedance 
Measuring range according to EN61557 is 0.25 
Ω ÷ 9.99kΩ. 
Measuring range (
Ω) Resolution 
(
Ω
Accuracy 
0.00 
÷ 9.99 
0.01 
10.0 
÷ 99.9 
0.1 
±(5 % of reading + 5 digits)
100 
÷ 999 
1.00k 
÷ 9.99k 
10 
± 10 % of reading 
 
Prospective fault current  (calculated value) 
Measuring range (A) 
Resolution (A) 
Accuracy 
0.00 
÷ 9.99 
0.01 
10.0 
÷ 99.9 
0.1 
100 
÷ 999 
1.00k 
÷ 9.99k 
10 
10.0k 
÷ 23.0k 
100 
Consider accuracy of fault 
loop resistance 
measurement 
 
The accuracy is valid if mains voltage is stabile during the measurement. 
 
Test current (at 230 V)...................... 6.5 A (10 ms) 
Nominal voltage range...................... 30 V 
÷ 500 V (45 Hz ÷ 65 Hz)