TESTBOY TV 450 
Technical specification 
 
65 
9.4.2 RCD selected 
 
Fault loop impedance  
Measuring range according to EN61557 is 0.46 
Ω ÷ 9.99 kΩ. 
Measuring range (
Ω) Resolution 
(
Ω
Accuracy 
0.00 
÷ 9.99 
0.01 
10.0 
÷ 99.9 
0.1 
±(5 % of reading + 10 digits) 
100 
÷ 999 
1.00k 
÷ 9.99k 
10 
   
± 10 % of reading 
Acccuracy may be impaired in case of heavy noise on mains voltage 
 
Prospective fault current (calculated value) 
Measuring range (A) 
Resolution (A) 
Accuracy 
0.00 
÷ 9.99 
0.01 
10.0 
÷ 99.9 
0.1 
100 
÷ 999 
1.00k 
÷ 9.99k 
10 
10.0k 
÷ 23.0k 
100 
Consider accuracy of fault 
loop resistance 
measurement 
 
Nominal voltage range...................... 30 V 
÷ 500 V (45 Hz ÷ 65 Hz) 
No trip out of RCD. 
R, XL values are indicative.  
 
9.5  Line impedance and prospective short-circuit current 
 
Line impedance 
Measuring range according to EN61557 is 0.25 
Ω ÷ 9.99kΩ. 
Measuring range (
Ω) Resolution 
(
Ω
Accuracy 
0.00 
÷ 9.99 
0.01 
10.0 
÷ 99.9 
0.1 
±(5 % of reading + 5 digits)
100 
÷ 999 
1.00k 
÷ 9.99k 
10 
± 10 % of reading 
 
Prospective short-circuit current (calculated value) 
Measuring range (A) 
Resolution (A) 
Accuracy 
0.00 
÷ 0.99 
0.01 
1.0 
÷ 99.9 
0.1 
100 
÷ 999 
1.00k 
÷ 99.99k 
10 
100k 
÷ 199k 
1000 
Consider accuracy of line 
resistance measurement 
 
Test current (at 230 V)...................... 6.5 A (10 ms) 
Nominal voltage range...................... 30 V 
÷ 500 V (45 Hz ÷ 65 Hz) 
R, XL values are indicative.