All fault messages can be transmitted to a primary recipient and up to 10 other
recipients, irrespective of the content.
A maximum of 20 values from the PA buffer can be monitored.
As is the case for each automatic SMS transmittal for INSYS GSM 4.2 LOGO!,
additional attempts will be made to transmit the message in the event of an error
(can be adjusted, default: 3 attempts).
Use of alarm inputs
Use of the two alarm inputs available on the INSYS GSM 4.2 LOGO! is restricted
when value monitoring is active.
If 1 to 10 values are being monitored, alarm input 2 is not available. If more than
10 values (11-20) are being monitored, alarm input 1 is also not available.
when value monitoring is active.
If 1 to 10 values are being monitored, alarm input 2 is not available. If more than
10 values (11-20) are being monitored, alarm input 1 is also not available.
Behavior after Reset or Power-Up
After a reset or power-up of the INSYS GSM 4.2 LOGO!, values in the PA buffer that
are outside the condition specified during parameter assignment do not result in
a fault message. The LOGO! status is accepted in this case without being
evaluated.
are outside the condition specified during parameter assignment do not result in
a fault message. The LOGO! status is accepted in this case without being
evaluated.
Timing
The shortest polling cycle is 1 s, i.e., signals of less than 1 s cannot be detected, in
general.
The PA buffer will not be polled if the INSYS GSM 4.2 LOGO! is occupied with any
of the following actions:
- Scan of field strength and login state, duration of approximately 5 s, interval of
general.
The PA buffer will not be polled if the INSYS GSM 4.2 LOGO! is occupied with any
of the following actions:
- Scan of field strength and login state, duration of approximately 5 s, interval of
60 s, can be disabled.
- Scan of SMS input memory and its execution, duration of approximately 5 s,
interval of 60 s, can be disabled.
- Existing GSM connection (data connection, DTMF connection, security
callback)
- Transmittal of an SMS, e.g., fault message, “alive” SMS (can be disabled),
power-up SMS (can be disabled), duration of approximately 10 s)