Configuration 
 
INSYS Modem 56k UL
 
14   Juni 
05
 
4.6.1  Alarm Trigger 
The alarm inputs are on HIGH potential provided 
by internal pull-up resistors as long as it is open. 
The alarm is activated by a simple connection to 
the ground potential. 
The alarm input is configured by the HSComm 
menu Configure 
Æ
 Alarm functions
• 
With alarm input active a simple alarm is 
triggered as soon as INPUT1 is set to ground 
potential for 4 seconds. 
• 
With impulse input active pulses (pulses and 
pauses with duration of 0,3 to 2 seconds) at 
INPUT1 are counted and processed after a 
delay of 5 seconds. If INPUT1 is  kept at ground potential for more than 4 seconds a 
simple alarm only is triggered for compatibility reasons. 
Activation of INPUT2 is interpreted like 2 pulses on INPUT1. 
Simple and impulse alarms can be triggered by software commands for control purposes.