HP Performance Optimized Data Center (POD) 20cp Manuale Di Servizio

Pagina di 81
 
Specifications  70 
Fire alarm panel connections 
The electrical layout of the fire alarm system is as described in the schematic drawing supplied with the HP 
POD 20c. 
 
Water specifications 
The following table describes the chilled water system specifications for the HP POD 20c. 
 
Feature 
Specification 
Facility input temperature to the HP POD 
20c 
12º to 24ºC (55º to 75ºF) 
Working pressure 
1,034 kPa (150 psi) 
HP POD 20c pressure drop 
172.4 kPa (25 psi) 
HP POD 20c water flow rate 
454 lpm (120 gpm) 
Chilled water supply and return 
connections 
Two DIN PN16 DN80 flanges 
 
 
Rack specifications 
Standard HP POD 20c racks (AT978A) 
  
Feature 
Specification 
U height 
50U 
Width 
54.6 cm (21.5 in) 
Depth 
99 cm (39 in)* 
Maximum load weight 
1,360.7 kg (3,000 lb) 
 
*This specification indicates the maximum clearance for the cold aisle. Equipment cannot exceed this measurement. 
 
Thermal and air flow performance 
 
Maximum thermal and air flow 
performance parameters 
HP POD 20c specification 
Air temperature—Inlet to 
rack-mounted components 
Dependent on IT configuration and 
chilled water inlet temperature 
Chilled water temperature 
12°C to 24°C (55°F to 75°F) 
Total rack-mounted component air 
flow 
Variable as required to maintain hot 
aisle setpoint temperature and 
dependent on IT configuration 
Heat rejection capacity 
300 kW 
 
 
Environmental specifications 
 
Feature 
Specification 
Operating temperature 
-28ºC to 54ºC (-18ºF to 130ºF) 
Non-operating temperature*  -29ºC to 54ºC (-20ºF to 130ºF)