HP Performance Optimized Data Center (POD) 20cp Manuale Di Servizio

Pagina di 81
 
Specifications  71 
Feature 
Specification 
Operating humidity 
 
0% to 100% external 
 
10% to 90% non-condensing internal 
Non-operating humidity* 
 
5% to 95% relative non-condensing 
 
39ºC (102ºF) maximum wet bulb 
temperature 
Operating altitude 
-76.2 m to 3,048 m (-250 ft to 10,000 ft) 
Non-operating altitude 
-76.2 m to 9,144 m (-250 ft to 30,000 ft) 
 
*For non-operating specifications, consider the temperature of computer and IT equipment inside the HP POD 20c. 
 
Optional features specifications 
  
Feature 
Specification 
Fire suppression 
3M Novec 1230 or FM200 fire extinguishing system provided in two canisters (main and 
reserve) 
Card reader 
12-key pad with 125 KHz proximity and 13.56 MHz contactless smart card 
Humidifier 
Provides 0.9-3.63 kg/hr (2-8 lb/hr) of water vapor into cold aisle to maintain POD 
environment within 20% to 80% relative humidity