HP Performance Optimized Data Center (POD) 20cp Guida Di Riferimento

Pagina di 37
 
Site requirements  13 
Requirement 
Location 
Specification 
Humidifier drain 
Cold aisle side (1) 
3.18 cm (1.25 in) drain line and 26.5 lpm (7 gpm) max 
 
 
Chilled water supply 
The following are the water quality requirements and specifications: 
 
Closed-loop water must not contain any lime scale deposits or loose debris. 
 
The temperature of the chilled water supplied to the HP POD 20c must be 12ºC to 24ºC (55ºF to 75ºF). 
  
 
CAUTION: 
 Freezing water can cause a blockage and damage to the unit. In outside locations 
that are subject to freezing temperatures, an additive such as glycol might be necessary to lower 
the freezing point. However, since the heat transfer potential of water with glycol is lower, the HP 
POD 20c must be de-rated accordingly. 
  
  
 
IMPORTANT:
  The chilled water system piping and heat exchangers must be drained completely, 
and then purged using compressed air when storing or transporting at or below freezing 
temperatures. 
  
  
 
IMPORTANT:
  Operating the chilled water system at the higher end of the acceptable range 
decreases the overall thermal capacity of the POD. 
  
Acceptable water quality specifications 
Water must be maintained per the following acceptable water quality standards. 
 
Parameter 
Range 
pH 
8.0–10 
Specific conductance at 25ºC (77ºF)  10–2500 µmhos 
Alkalinity ("M" as CaCO
3
150–1000 ppm 
Sulfur (SO
4
0–150 ppm 
Chloride (Cl) 
0–100 ppm 
Hardness (CaCO
3
0–350 ppm 
Calcium hardness (CaCO
3
0–200 ppm 
Magnesium hardness (CaCO
3
0–150 ppm 
Copper (Cu) 
< 0.20 ppm 
Iron (Fe) 
< 3.0 ppm 
Aluminum (Al) 
< 0.50 ppm 
Sodium (Na) 
0–1000 ppm 
Silica (SiO
2
0–150 ppm 
Zinc (Zn) 
< 1.0 ppm 
Manganese (Mn) 
< 0.1 ppm 
Phosphate Ortho- (PO
4
)   
< 3 ppm 
Bacteria 
< 1000 CFU/ml 
Suspended solids 
< 10 ppm 
 
If your water is out of range, consult a water quality expert. 
The following table describes the chilled water system specifications for the HP POD 20c.