HP Performance Optimized Data Center (POD) 20cp Guida Di Riferimento

Pagina di 37
 
Site requirements  14 
 
Feature 
Specification 
Facility input temperature to the HP POD 
20c 
12º to 24ºC (55º to 75ºF) 
Max design pressure 
1,034 kPa (150 psi) 
HP POD 20c pressure drop 
172.4 kPa (25 psi) 
HP POD 20c water flow rate 
454 lpm (120 gpm*) 
Chilled water supply and return 
connections 
Two 7.62 cm (3 in) ASME B16.5 
class #150 flanges 
 
*Measurement is in US gallons per minute. 
 
Piping materials 
Do not use the following interconnecting piping materials in a closed water system: 
 
Oxidizing biocides 
 
Aluminum components 
 
Brass components with high levels of zinc 
 
Non-stainless steel iron components 
 
PVC 
  
 
IMPORTANT:
  Even though some PVC grade piping materials are designed to handle the 
expected water pressure, the use of PVC materials should be reviewed and approved by the 
customer site engineers. 
  
 
Power infrastructure installation 
When determining the final location of the power connections, consider the following: 
 
Distance between the facility utilities and the location of the HP POD 20c 
 
Distance between possible UPS or generator locations and the HP POD 20c 
 
Requirements for routing electrical feeders (underground or overhead) 
The facility power connection must be installed in compliance with local electrical codes and regulations. HP 
reference electrical installation design is based on a maximum distance of 15.2 m (50 ft) or a line of sight 
between the disconnect and the HP POD 20c. 
 
Site electrical system 
To ensure a complete and safe integration of the HP POD solution with your facility, HP requires that you 
complete the following actions for the installed electrical system prior to the installation of the HP POD 
solution: 
 
Short circuit analysis 
 
Arc flash study 
 
Circuit breaker coordination study