HP Performance Optimized Data Center (POD) 20cp Manuale Utente
Component identification 17
Item
Component
Description
1
VESDA air sampling smoke
detection unit
An early warning, laser scan smoke detection unit
2
Fire alarm and suppression
release control panel
•
Controls all fire systems within the HP POD 20c, including the
smoke detection system, fire suppression system, fire pulls, and
so on
•
Includes a battery backup system that provides backup power
to the fire system during a utility power loss
3
ECS relays and ECS modules
Relays for the ECS control, ECS communications, I/O connections,
and terminal block connections
4
EPO controller board and house
panel fuses
panel fuses
Connections for the EPO system and fuses for other house panel
components
components
5
Dual power supplies with
battery backup
Provides 24 V DC power to the PLC, LED lighting, and ECS systems
HP POD 20c racks
The HP POD 20c contains a total of ten IT racks.
CAUTION:
If any racks contain empty RU space, use the HP POD 20c filler panels to maintain
the efficiency of the HP POD 20c thermal system. Filler panels are available from HP in 10-pack
quantities (part number AQ682A) and 100-pack quantities (part number AS993A).
For more information about racks and network cabling, see the HP Performance Optimized Datacenter
Networking Guide.