HP Performance Optimized Data Center (POD) 20cp Manuale Utente

Pagina di 86
 
Life safety systems  19 
For the location of EPO buttons, see "Life safety component identification (on page 
)." 
The EPO system must be reset before you can power up and restart the HP POD 20c. To reset the EPO system: 
1. 
Verify that the key control for the EPO mode is in the Armed position. 
2. 
Press the white EPO Reset button. 
If you triggered the EPO system manually, you must reset the EPO button that you pressed to the Active 
position. 
 
ECS touchscreen and EPO indicators 
The ECS touchscreen and EPO indicators are located on the door to the control panel.   
The touchscreen enables you to easily configure the environmental parameters, access data, and monitor 
environmental, life safety, and access control conditions within the HP POD 20c. 
The EPO indicators provide EPO status. The EPO key control and EPO reset button enable you to adjust the 
EPO system mode. 
 
 
Item  Component 
Indicator Color 
Description 
Source A available indicator 
White 
Indicates the EPO power status for main 
power feed A 
Source A wrong rotation indicator  Red 
Indicates the Source A power phase 
rotation is incorrect  
Source B wrong rotation indicator  Red 
Indicates the Source B power phase 
rotation is incorrect  
Source B available indicator 
White 
Indicates the EPO power status for main 
power feed B 
EPO shutdown indicator 
Red 
Indicates an EPO shutdown or alarm 
situation 
EPO armed indicator 
White 
Indicates that the EPO system is armed and 
operational 
EPO reset button 
Blue 
Resets the EPO system when pressed