HP Performance Optimized Data Center (POD) 20cp Manuale Utente
Maintenance 77
Maintenance
Periodic maintenance
Perform periodic inspections to ensure that the HP POD 20c continues to perform according to design
parameters. During periodic inspections, pay special attention to electrical connections and wiring.
For more specific maintenance information, see the HP Performance Optimized Datacenter 20c
parameters. During periodic inspections, pay special attention to electrical connections and wiring.
For more specific maintenance information, see the HP Performance Optimized Datacenter 20c
Maintenance and Service Guide.
Sample HP POD 20c maintenance schedule
For detailed maintenance information and schedules, consult with HP services.
The following table is a sample maintenance schedule for an HP POD 20c. For more detailed maintenance
The following table is a sample maintenance schedule for an HP POD 20c. For more detailed maintenance
information, see the HP Performance Optimized Datacenter 20c Maintenance and Service Guide.
Component to be inspected
Frequency
Electrical connections and wiring—Visual
Every 30 days
Electrical connections and wiring—Thermal scans
Every 180 days
Condensation and drainage system (leaks)—Visual
Every 30 days
Condensation and drainage system (leaks)—Functional
Every 90 days
Busway interconnects (tightened)
Every 180 days
EPO system
Every 180 days
Third-party OEM components (fire alarm and suppression system, humidifier,
and so on)
For more information about the
components, see the Operation
and Maintenance manual for
the HP Performance Optimized
the HP Performance Optimized
Datacenter 20c.