HP Performance Optimized Data Center (POD) 20cp Manuale Utente

Pagina di 86
 
Regulatory information  79 
Regulatory information 
HP POD 20c regulatory compliance 
The HP POD 20c complies with the following regulatory standards. 
  
Standard  Certification level 
Standard title 
IEC/EN 
60950 
"Intertek Tested and 
Certified" 
 
IEC/EN 60950—Standard for Safety Information Technology 
Equipment, Part 1: General Requirements, Issue: 2006 
 
IEC/EN 60950—Standard for Safety Information Technology 
Equipment, Part 22: Equipment to be Installed Outdoors, Issue: 
2006 
IBC 2009 
Designed to Comply 
With the applicable 
requirements 
2009 International Building Code, © 2010 International Code 
Council, Inc. 
 
 
Safety and IEC compliance 
The HP POD 20c is examined, tested, and found to be in compliance with IEC/EN 60950 Part 1 and Part 
22 as an Information Technology Product. For more information, see "HP POD 20c regulatory compliance 
(on page 
)." 
The HP POD 20c is not suitable for long-term human occupancy. The HP POD 20c is Listed as a Product that 
provides service access areas for periodic maintenance and service. These areas must be used only by 
owner-authorized and qualified personnel who are trained in the maintenance and service of the HP POD 
20c components. 
  
 
IMPORTANT:
  Before installing the HP POD 20c, consult your local Authorities for applicable 
regulations and to review site-specific location guidelines. If needed, obtain any necessary 
permits. 
  
Additional considerations for safety and Electrical compliance are as follows: 
 
The HP POD 20c is Certified as an Information Technology Product to IEC/EN 60950 Part 1 and Part 
22. 
 
The HP POD 20c is evaluated as a "non-inhabitable product" that provides "service access" areas for 
customer-authorized, qualified, and trained service personnel. 
 
The electrical connections of the HP POD 20c are evaluated as feeder connections for connection to an 
existing facility, and are not suitable as "service entrance" for connection to the utility. 
 
The HP POD 20c is designed for stationary installation outdoors in a Pollution Degree 3 environment, 
in restricted access locations, with field wiring terminals provided for permanent supply connections. 
 
The HP POD 20c meets the following ratings.   
 
Feature 
Specification 
Category 
Rated Overvoltage Category III 
Protection 
Surge protection device