7.  Servo Parameters  
7.4  Supplement 
 
168 
 
(c)  Setting the output scale 
When “0“ is set, the output will be made with the standard output unit. To change the output unit, 
set a value other than “0”. 
The scale is set with a 1/256 unit.  When 256 is set, the unit will be the same as the standard 
output. 
 
# No. 
Abbrev Parameter 
name 
2263 
SV063 
DA1MPY 
D/A output channel 1 
output scale 
2264 
SV064 
DA2MPY 
D/A output channel 2 
output scale 
 
(Example 1)  When SV061 = 5, SV063 = 2560 
The V-phase current value will be output with 1 A/V unit to D/A output ch.1. 
 
(Example 2)  When SV063 = 11, SV064 = 128 
The position droop will be output with a 2mm/Vunit to D/A output ch.2.