5.4.7 "District 
hot 
water" menu (DIST.HEATING) 
The parameters in this menu refer to the type of the respective 
district hot-water station and the associated specific control 
functions. 
 
Para-
meter 
Designation 
Setting range / Setting values 
Factory 
setting 
Setting 
01 
Increase 
OFF, –10 to 50 K 
 
02 
Maximum limit of 
flow temperature 
setpoint 
10 ... 130 
°C 
90  
03* Minimum 
district 
heating valve 
stroke 
0 ... 50 % 
10 
 
04 Secondary 
flow 
boost 
0,1 ... 30 %/K 
 
05 
Adjustment time 
0 ... 60 min 
 
06 
Runtime of district 
heating valve 1 
10 ... 1800 s 
120 
 
07* 
Runtime of district 
heating valve 2 
10 ... 1800 s 
30 
 
08* Maximum 
return 
temperature 
setpoint 
0 ... 100 
°C 
90  
09* Application 
point 
variable district 
heating return 
temperature 
OFF, –40 to +10 
°C 
OFF  
10* Maximum 
return 
temperature 
setpoint with hot 
water circuit 
charge 
0 ... 100 
°C 
90