Honeywell EN2H-0221GE51 R0808 ユーザーズマニュアル
Operation
SDC / DHC
104 EN2H-0221GE51
R0808
* OEM
5.4.7 "District
hot
water" menu (DIST.HEATING)
The parameters in this menu refer to the type of the respective
district hot-water station and the associated specific control
functions.
district hot-water station and the associated specific control
functions.
Para-
meter
meter
Designation
Setting range / Setting values
Factory
setting
setting
Setting
01
Increase
OFF, –10 to 50 K
0
02
Maximum limit of
flow temperature
setpoint
flow temperature
setpoint
10 ... 130
°C
90
03* Minimum
district
heating valve
stroke
stroke
0 ... 50 %
10
04 Secondary
flow
boost
0,1 ... 30 %/K
5
05
Adjustment time
0 ... 60 min
3
06
Runtime of district
heating valve 1
heating valve 1
10 ... 1800 s
120
07*
Runtime of district
heating valve 2
heating valve 2
10 ... 1800 s
30
08* Maximum
return
temperature
setpoint
setpoint
0 ... 100
°C
90
09* Application
point
variable district
heating return
temperature
heating return
temperature
OFF, –40 to +10
°C
OFF
10* Maximum
return
temperature
setpoint with hot
water circuit
charge
setpoint with hot
water circuit
charge
0 ... 100
°C
90