Honeywell EN2H-0221GE51 R0808 ユーザーズマニュアル

ページ / 258
SDC / DHC 
Operation 
EN2H-0221GE51 R0808 
105 
Para-
meter 
Designation 
Setting range / Setting values 
Factory 
setting 
Setting 
0 Temperature 
(parameters 12 through 
15 are not displayed) 
0  
Volume flow and 
temperature (parameters 
12 through 14 are not 
displayed) 
 
 
11* 
Return limit of 
district heating 
valve 
Heat output and 
temperature (parameters 
13 through 15 are not 
displayed) 
 
 
12* Calibration 
of 
heat 
output 
1 ... 9999 
 
13* Calibration 
of 
volume flow 
1 ... 9999 
 
14* Maximum 
heat 
output 
1 ... 9999 kW 
9999 
 
15* Maximum 
volume 
flow 
0,01 ... 99.99 m
3
/h 99.99 
 
 
* OEM 
 
 
5.4.8  "Return increase" menu (RETURN CONTR) 
The parameters in this menu refer to special settings with regard 
to the increase in return temperature with heat generators.  
Enabling occurs only with corresponding activation in the 
"Hydraulics" menu. 
 
Para-
meter 
Designation 
Setting range / Setting values 
Factory 
setting 
Setting 
01 Return 
temperature 
setpoint 
10 ... 95°C 
20 
 
02 Switch-off 
differential 
1 ... 20 K 
2  
 
03 
Follow-up time of 
pump 
0 ... 60 min