Operation 
SDC / DHC  
106 EN2H-0221GE51 
R0808 
5.4.9  "Solar" menu (SOLAR) 
The parameters in this menu refer to special settings with regard 
to the solar applications.  
Enabling occurs only with corresponding activation in the 
"Hydraulics" menu. 
 
Para-
meter 
Designation 
Setting range / Setting values 
Factory 
setting 
Setting 
01 Switch-on 
differential 
(Setting value of parameter  
02 + 3 K) to 30 K 
10  
02 Switch-off 
differential 
2 K to (setting value of parameter 
01 – 3 K) 
5  
03 Minimum 
runtime 
of solar charging 
pump 
0 ... 60 min 
 
04 Collector 
maxi-
mum temperature 
OFF, 70 to 210°C 
210 
 
05 Buffer 
maximum 
temperature limit 
20 ... 110°C 
75 
 
1 Priority 
operation 
2 Parallel 
operation 
Priority operation of hot-
water circuit 
06 Operating 
mode 
Priority operation of 
buffer 
 
 
07 Heat 
generator 
cycle inhibitor 
(only if parameter 
06 = 1) 
OFF, 0.5 to 24 h 
OFF 
 
08 Solar 
priority 
parallel switchover 
OFF, 1 to 30 K 
OFF 
 
OFF 
No heat balancing 
Heat balancing via flow-
through calculation 
09 Heat 
balance 
Heat balancing via pulse 
input 
OFF