Honeywell EN2H-0221GE51 R0808 ユーザーズマニュアル
Operation
SDC / DHC
106 EN2H-0221GE51
R0808
5.4.9 "Solar" menu (SOLAR)
The parameters in this menu refer to special settings with regard
to the solar applications.
to the solar applications.
Enabling occurs only with corresponding activation in the
"Hydraulics" menu.
"Hydraulics" menu.
Para-
meter
meter
Designation
Setting range / Setting values
Factory
setting
setting
Setting
01 Switch-on
differential
(Setting value of parameter
02 + 3 K) to 30 K
02 + 3 K) to 30 K
10
02 Switch-off
differential
2 K to (setting value of parameter
01 – 3 K)
01 – 3 K)
5
03 Minimum
runtime
of solar charging
pump
pump
0 ... 60 min
3
04 Collector
maxi-
mum temperature
OFF, 70 to 210°C
210
05 Buffer
maximum
temperature limit
20 ... 110°C
75
1 Priority
operation
2 Parallel
operation
3
Priority operation of hot-
water circuit
water circuit
06 Operating
mode
4
Priority operation of
buffer
buffer
07 Heat
generator
cycle inhibitor
(only if parameter
06 = 1)
(only if parameter
06 = 1)
OFF, 0.5 to 24 h
OFF
08 Solar
priority
parallel switchover
OFF, 1 to 30 K
OFF
OFF
No heat balancing
1
Heat balancing via flow-
through calculation
through calculation
09 Heat
balance
2
Heat balancing via pulse
input
input
OFF