SDC / DHC 
Operation 
EN2H-0221GE51 R0808 
107 
Para-
meter 
Designation 
Setting range / Setting values 
Factory 
setting 
Setting 
10 Reset 
heat 
balance 
SET by pressing the input button  – 
 
11 
Volume flow 
0 ... 30 L/min or L/pulse 
 
12 
Density of medium  0.8 ... 1.2 kg/L 
1.05 
 
13 
Heat capacity of 
medium 
2 ... 5 KJ/kgK 
3.6 
 
14 Final 
switch-off 
temperature 
OFF, 90 to 210 °C 
210  
 
15 
Test cycle of solar 
charging 
switchover 
1 ... 60 min 
10 
 
16 Switchover 
tem-
perature 
20 ... 110 °C 
75  
 
 
 
5.4.10  "Solid" menu (SOLID FUEL) 
The parameters in this menu refer to special settings with regard 
to solids regulation.  
Enabling occurs only with corresponding activation in the 
"Hydraulics" menu. 
 
Para-
meter 
Designation 
Setting range / Setting values 
Factory 
setting 
Setting 
01 Minimum 
temperature 
20 ... 80 °C 
60 
 
02 Maximum 
temperature 
30 ... 100 °C 
90 
 
03 Switch-on 
differential 
(Setting value of parameter  
04 + 3 K) to 20 K 
10  
04 Switch-off 
differential 
2 K to (setting value of parameter 
03 – 3 K) 
5  
05 Heat 
generator 
cycle inhibitor 
OFF, 2 to 180 min 
OFF