Honeywell EN2H-0221GE51 R0808 ユーザーズマニュアル
SDC / DHC
Operation
EN2H-0221GE51 R0808
107
Para-
meter
meter
Designation
Setting range / Setting values
Factory
setting
setting
Setting
10 Reset
heat
balance
SET by pressing the input button –
11
Volume flow
0 ... 30 L/min or L/pulse
0
12
Density of medium 0.8 ... 1.2 kg/L
1.05
13
Heat capacity of
medium
medium
2 ... 5 KJ/kgK
3.6
14 Final
switch-off
temperature
OFF, 90 to 210 °C
210
15
Test cycle of solar
charging
switchover
charging
switchover
1 ... 60 min
10
16 Switchover
tem-
perature
20 ... 110 °C
75
5.4.10 "Solid" menu (SOLID FUEL)
The parameters in this menu refer to special settings with regard
to solids regulation.
to solids regulation.
Enabling occurs only with corresponding activation in the
"Hydraulics" menu.
"Hydraulics" menu.
Para-
meter
meter
Designation
Setting range / Setting values
Factory
setting
setting
Setting
01 Minimum
temperature
20 ... 80 °C
60
02 Maximum
temperature
30 ... 100 °C
90
03 Switch-on
differential
(Setting value of parameter
04 + 3 K) to 20 K
04 + 3 K) to 20 K
10
04 Switch-off
differential
2 K to (setting value of parameter
03 – 3 K)
03 – 3 K)
5
05 Heat
generator
cycle inhibitor
OFF, 2 to 180 min
OFF