6.8.2  Heating circuit outside temperature assignment  
Function active only when using a second outside sensor! 
 
If in the central device a second outdoor sensor (AF2) was 
connected to a variable input and registered, the heating circuit 
can be assigned either to the outside sensor 1, 2 or to the mean 
value of both sensors. 
 
For each outside sensor the following applies: 
In case of a defect affecting a sensor, switching to the remaining 
outside sensor with simultaneous fault indication occurs 
automatically. In case of a defect affecting both sensor circuits the 
heating circuit is regulated on the basis of a set heating 
characteristic curve and heating program corresponding to a 
fictitious outside temperature of 0°C with regard to the set 
minimum temperature. 
 
5.2.5 "Direct Heating Circuit" / "Mixed Heating Circuit 1" / "Mixed 
Heating Circuit 2" menu, Pg. 78 
 
6.8.3  Outside temperature emergency operation value  
If a connected outside sensor fails during weather condition-
controlled operation (sensor short-circuit or interruption), 
emergency operation takes effect. 
Weather condition-based control then adjusts the temperature 
based on an assumed fixed outside temperature specified via a 
parameter value. 
Designation 
Key/Menu 
Parameter 
Characteristic curve for 
emergency operation without 
outside sensor 