Control Functions 
SDC / DHC  
122 EN2H-0221GE51 
R0808 
6.8.4  Outside temperature disable  
The purpose of outside temperature disable is to prevent the heat 
generator from starting up above a defined outside temperature. 
If several heat generators are controlled though one device 
(automatic stoker, 2-stage), all stages of the device will be 
disabled with outside temperature disable. 
In the case of cascaded systems with multiple devices, the entry 
of an outside temperature disable is possible for each central 
device so that individual levels can be blocked by the outside 
temperature disable. 
6.8.5  Climate zone  
The climate zone is the coldest outside temperature value to be 
expected. 
For the heat demand coverage, this value is taken as the basis for 
the design of the heating system. 
This parameter defines the corresponding slope value of the 
heating curve of the heating circuit with regard to the climate 
zone. 
 
5.2.3 "System Parameters" menu, Pg. 72 
 
6.8.6  Design temperature  
Until now, configuration of the heating curve calculation occurred 
via the values 
•  Climate zone (T
ANorm
•  Slope (S) 
•  Heating system (m value) 
Supplemental to the slope, the setting of the design temperature 
T
VLNorm
 is also possible directly at the controller.  
Setting range DESIGN TEMP: Setting range HC
min
 to HC
max
 (°C) 
There is a direct relation between the HEATING CURVE and 
DESIGN TEMP parameters in the following connection: 
C
S
T
C
T
ANorm
VLNorm
°
+
°
=
20
*
)
20
(
 
This means that the value of the respective other parameter 
changes accordingly. 
Function
Function
See also