Honeywell EN2H-0221GE51 R0808 ユーザーズマニュアル

ページ / 258
SDC / DHC 
Control Functions 
EN2H-0221GE51 R0808 
123 
The display for the heating curve adjustment occurs in 
combination, i.e. the design temperature (bottom right) and the 
slope (bottom left) are displayed and set in one display. Both flash 
during adjustment. 
The parameter (display above) is still HEATING CURVE. 
The jump occurs via the "Direct Heating Circuit" or "Mixed Heating 
Circuit 1"/"Mixed Heating Circuit 2" menu and the heating curve 
parameter. 
 
6.8.7  Summer switch-off  
This function is only effective in control mode AUTOMATIC. 
 
For higher outside temperatures, normally above 20°C, it does not 
make sense to keep the heating on in the building. You can thus 
choose to switch-off heating depending on the outside 
temperature according to the following criteria: 
 
Outside temperature rise 
A switch-off is initiated when the mean outside temperature 
exceeds the set value. 
11,0
12,0
13,0
14,0
15,0
16,0
17,0
18,0
19,0
20,0
21,0
22,0
23,0
00:
00
01:
00
02:
00
03:
00
04:
00
05:
00
06:
00
07:
00
08:
00
09:
00
10:
00
11:
00
12:
00
13:
00
14:
00
15:
00
16:
00
17:
00
18:
00
19:
00
20:
00
21:
00
22:
00
23:
00
00:
00
T /˚C
-1 K
a
b
c
d
 
 
a  Current outside temperature 
c  Summer switch-off on 
b  Mean outside temperature 
d  Set value 
 
NOTE
Function