Hydraulic Components 
SDC / DHC  
248 EN2H-0221GE51 
R0808 
The last (most recent) fault message is in first position; the 
previous fault messages are shifted down by a position with each 
new fault message. The fifth fault message is deleted when a new 
fault message appears. 
 
Operating 
information 
Key/Menu 
Parameter 
Display of logical 
fault messages 
SYSTEM 13 
Fault memory 
inquiry 
FAULT MESSAGE 
ERR-1 . ERR-5 
 
In the case of condensing systems with automatic stokers, the 
outside sensor input can be used to switch off the heating system. 
A sensor short-circuit at the outside sensor suppresses a fault 
message regarding this and switches off the system. The 
message "Heating system off" appears instead of the fault 
message in this case. 
If a heat generator defect occurs (fault message 30-1 or 31-3) and 
system frost protection is active at the same time, boiler start-up 
protection is switched off and thus the heating circuit pumps are 
started to minimise the danger of system freezing. 
7.4.1 Basic 
display/fault stack fault messages 
With connection of an automatic stoker, further fault messages 
may arrive from it. They are displayed as follows. 
 
Fault type 
Fault 
code 
Field 1 
Field 2  Field 3 
Water 
pressure 
S0-1 Water 
pressure 
 
HIGH 
Water 
pressure 
S0-5 Water 
pressure 
 
LOW 
Water 
pressure 
S0-2 Water 
pressure 
 
MIN 
Ventilation S1-0 Ventilation   
 
Maintenance S2-0  Maintenance   
 
Switch-off –  Switch-off   
OFF 
Service 240-1 
Service     
NOTE