Technical data 
SDC / DHC  
250 EN2H-0221GE51 
R0808 
8 Technical 
data 
8.1 General 
Mains connection 
voltage 
230 V +6 % / –10 % 
Rated frequency 
50 ... 60 Hz 
Power consumption 
max. 5.8 VA 
Pre-fuse 
max. 6.3 A slow-blowing 
Contact load of the 
output relays 
2 (2) A 
Bus interface 
For the connection of external devices (wall device, PC, modem 
or gateway)  
Max. bus length 
50 m 
Power supply via bus 
12 V/150 mA 
Ambient temperature 
0 ... +50°C 
Storage temperature 
–25 ... +60°C 
Degree of protection 
IP 30 
Protection class as per 
EN 60730 
II 
Protection class as per 
EN 60529 
III 
Radio protection 
EN 55014 (1993) 
Interference resistance  EN 55104 (1995) 
EC conformity 
89/336/EEC 
Housing dimensions 
144 x 96 x 75 mm (W x H x D) 
Housing material 
ABS with static inhibitor 
Connection technology  Plug-in screw terminal connections