Honeywell EN2H-0221GE51 R0808 ユーザーズマニュアル

ページ / 258
SDC / DHC 
Hydraulic Components 
EN2H-0221GE51 R0808 
249 
7.4.1.1  Sensor calibration  
If the measured values of the connected sensors do not match 
the actual temperatures, a comparison of the sensor values is 
possible in the "Sensor Comparison" menu. In this menu, all 
sensors connected to the device can be corrected by ±5 K based 
on the factory calibration value. 
The current measured value, plus or minus the correction made 
and the correction itself, appears in the display. The increment of 
the compensation is 0.5 K. 
 
 ATTENTION 
The sensor circuits are calibrated at the factory using precise 
measuring equipment. Compensation should only be carried 
out if you are sure that the amount of the deviation remains 
constant over the entire measurement range. 
With sensor compensation, the respective amount must be 
noted down, as otherwise the factory setting is no longer 
valid and the reference value is lost. 
The original factory setting cannot be restored via a reset! 
 
•  Compensation in the case of very longer sensor cables 
•  Constant external temperature influence on sensors 
 
7.4.1.2  Full controller reset  
To revert the controller to its state of delivery, a full reset can be 
performed. Here, all parameters, values and counters accessible 
via the enabled code are reset and the controller is restarted. 
Values that are not accessible via the set access code remain in 
tact. 
 
Press the 
¢
¥
¦
 and 
§
 keys simultaneously 
 
7.4.1.3 Controller 
time 
correction 
In some special cases it may be necessary to adjust the runtime 
of the clock integrated in the controller. Please contact the 
manufacturer if necessary. 
 
Function
Application
Activation