Honeywell EN2H-0221GE51 R0808 ユーザーズマニュアル

ページ / 258
Technical data 
SDC / DHC  
252 EN2H-0221GE51 
R0808 
8.2.2 PT 
1000 
For variable input 1 (VI-1) (setting of exhaust gas sensor), 
collector flow sensor (SPFS) 
°C 
Ω 
°C 
Ω 
°C 
Ω 
°C 
Ω 
1000.00 80 
1308.93 140 
1535.75 280 
2048.76 
10 
1039.02 85 
1327.99 150 
1573.15 300 
2120.19 
20 
1077.93 90 
1347.02 160 
1610.43 320 
2191.15 
25 
1093.46 95 
1366.03 170 
1647.60 340 
2261.66 
30  1116.72 
100 1385.00 
180 1684.65 
360 2331.69 
40  1155.39 
105 1403.95 
190 1721.58 
380 2401.27 
50  1193.95 
110 1422.86 
200 1758.40 
400 2470.38 
60  1232.39 
115 1441.75 
220 1831.68 
450 2641.12 
70  1270.72 
120 1460.61 
240 1904.51 
500 2811.00 
75  1289.84 
130 1498.24 
260 1976.86 
–  – 
 
8.3  Sensor measurement ranges 
Designation 
Brief description 
Sensor type 
Measurement 
range 
Outside sensor  
AF 
NTC 20  
–50 °C to 90 °C 
Heat generator sensor  
KF 
NTC 20  
–50 °C to 120 °C 
Flow sensor 1 
VF1 
NTC 20  
–50 °C to 120 °C 
Flow sensor 2 
VF2 
NTC 20  
–50 °C to 120 °C 
Tank sensor 
SF 
NTC 20  
–50 °C to 120 °C 
Collector flow sensor 
KVLF 
PT 1000 
–50 °C to 210 °C 
Collector tank/buffer 
sensor 
KSPF 
NTC 20  
–50 °C to 120 °C 
Variable input VI-1*) 
VE1 
NTC 20  
PT 1000 
–50 °C to 120 °C 
–50 °C to 500 °C 
Variable input VI-2 
VE2 
NTC 20  
–50 °C to 120 °C 
Variable input VI-3 
VE3 
NTC 20  
–50 °C to 120 °C 
 
*)  Depending on the selection of the assigned function.  
PT 1000 e.g. for exhaust gas sensor connection.