Technical data 
EN2H-0221GE51 R0808 
251 
8.1.1 Installation 
recommendations 
Mains voltage lines  
(mains connection, burners, pumps, servo motors): 
Diameter 1.5 
mm
2
 
Max. permissible length 
No limit for installation in buildings. 
Safety low-voltage lines  
(sensors, ext. switches upon demand via switching contact, modem connection lines, analog 
signal lines etc.) 
Diameter 0.5 
mm
2
 
Max. permissible length 
100 m (looped circuit); longer connection lines should be avoided 
to prevent the risk of interference 
Data bus lines 
Diameter 0.6 
mm
2
 
Max. permissible length 
50 m (looped circuit, longest distance between a central device 
and a device to be supplied); longer connection lines should be 
avoided to prevent the risk of interference. 
Recommended layouts 
J-Y(St)Y 2 x 0.6 
 
8.2  Sensor resistance values 
8.2.1 NTC 
20 
For outside sensor (OT), heat generator sensor (BLRS/BS), tank 
sensor (DHWS), mixed heating circuit 1 flow sensor (VF1), mixed 
heating circuit 2 flow sensor (VF2), variable input 1 (VI-1) (setting 
not for exhaust gas sensor), variable input 2 (VI-2), variable input 3 
(VI-3), collector tank/buffer sensor (SBUS). 
°C 
kΩ 
°C 
kΩ 
°C 
kΩ 
°C 
kΩ 
–20 220.6 
70.20 
20  25.34 
70  3.100 
–18 195.4 
63.04 
25  20.00 
75  2.587 
–16 173.5 
56.69 
30  15.88 
80  2.168 
–14 154.2 
51.05 
35  12.69 
85  1.824 
–12 137.3 
46.03 
40  10.21 
90  1.542 
–10 122.4 
10  41.56 
45  8.258 
95  1.308 
–8 109.2 
12 37.55 
50 6.718 
100 1.114 
–6 97.56 
14 33.97 
55 5.495 
–  – 
–4 87.30 
16 30.77 
60 4.518 
–  – 
–2 78.23 
18 27.90 
65 3.734 
–  –