TROUBLESHOOTING
Continued 
OBSERVED PROBLEM
Moisture/condensation  noticed 
on windows
Heater produces a whistling noise 
when burner is lit
White  powder  residue  forming 
within burner box or on adjacent 
walls or furniture
Remote does not function
POSSIBLE CAUSE
1. Not enough combustion/ven-
tilation air
1. Turning control knob to HI 
position when burner is cold
2. Air in gas line
3. Air passageways on heater 
blocked
4. Dirty  or  partially  clogged 
burner orifice
1. When  heated,  vapors  from 
furniture polish, wax, carpet 
cleaners, etc. may turn into 
white powder residue
1. Battery is not installed.  
Battery power is low
REMEDY
1. Refer to Air for Combustion 
and Ventilation requirements 
(page 5)
1. Turn  control  knob  to  LO 
position and let warm up for 
a minute
2. Operate  burner  until  air  is 
removed from line. Have gas 
line checked by local natural 
or propane/LP gas company
3. Observe  minimum  installa-
tion clearances (see pages 9 
through 12)
4. Clean  burner  (see  Cleaning 
and Maintenance, page 23) or 
replace burner orifice
1. Turn  heater  off  when  using 
furniture polish, wax, carpet 
cleaners or similar products
1. Replace  9-volt  batteries  in 
receiver and hand-held remote 
control