Digital Control User Input Confi guration
The adjustable control dip switches are located at the lower left hand portion of the digital Smart Center.  The inputs are only visible 
and accessible with the front cover removed from the PTAC.
Dip Switch Setting
1) Electronic Temperature Limiting – Switches 1-4
The digital control is set from the factory to allow a tempera-
ture range between 60°F and 90°F in both heating and cooling 
mode. Dip Switches 1-4 can be used to set high and low limits 
for either heating or cooling or both.
From the factory all four switches are in the up ‘ON’ position. 
The charts to the right show the available electronic limiting 
ranges.
2) Fan Cycle Control – Switch 5
All PTACs are shipped from the factory with Dip Switch 5 in the 
OFF’ position to cycle the fan only when there is a demand for 
the compressor or heater. As an option the fan may be set to 
‘continuous’ mode by switching Dip Switch 5 to ‘ON’ position to 
run the fan continuously while the unit is powered on. 
To ensure that the room temperature is maintained evenly while 
in fan cycle mode the Even Temp Load Anticipation feature is 
enabled. Quiet Fan Delay is also enabled in fan cycle mode to 
lessen the acoustical change between compressor start up and 
shut off by running the fan for 5 seconds before each demand 
cycle, and 30 seconds after cooling or 15 seconds after heating 
cycles.
3) Room Freeze Protection – Switch 6
Units are shipped from the factory with the room freeze protection 
disabled.  Room  Freeze  Protection  can  be  switched  on  at  the 
owner’s preference by moving Dip Switch 6 to ‘ON’. This feature 
will monitor the indoor room conditions and in the event that the 
room falls below 40°F the unit will cycle on high fan with the 
electric heater. This occurs regardless of mode.
4) Emergency Heat Override – Switch 7
In the unlikely event of a compressor failure a heat pump unit 
may be switched to operate in only the electric heat mode until 
repairs can be made. Moving Dip Switch 7 to ‘ON’.
Note: PTAC must be disconnected from power supply 
when making any confi guration changes.
Temperature 
Range
Dip 
Switch
Low
High
3
4
60
90
On
On
63
90
On
Off
66
90
Off
Off
69
90
Off
On
Cooling Range Switches 3 & 4
Heating Range Switches 1 & 2
Temperature 
Range
Dip          
Switch
Low
High
1
2
60
90
On
On
60
87
Off
On
60
84
Off
Off
60
81
On
Off
Figure 11  
Factory Dip Switch Confi guration