Bryan Boilers Triple-Flex 150 ユーザーズマニュアル

ページ / 81
 
Date:  
8-4-2010 
 
Revision: 0 
 
Form:  
2396
 
the touch panel display.  There is a soft 
switch (paragraph 2.2.11) provided with the 
SOLA hydronic control that will put the boiler 
into standby for an indefinite period of time. 
 
WARNING: 
The boiler on / off switch will not turn 
off the 3 phase high voltage power to 
the motor. 
7.  The boiler lockout reset button is a push 
button used to reset the hydronic control 
after a boiler failure. 
8.  The power on light will be white in color and 
indicates that there is 120 volts ac being 
supplied to electrically connected devices. 
9.  The enabled light will be green in color and 
indicates that the boiler is enabled.  Enabled 
is a state in which the boiler is allowed to 
operate within the boiler’s predefined 
parameters. 
10. The fuel on light will be amber in color and 
indicates that the boiler is firing and 
producing heated water. 
11. The boiler lockout light will be red in color 
and indicates that the boiler has failed.  The 
SOLA control will have additional 
information displayed on the touch panel 
display.  These failures will be explained in 
section 2.3.9. 
2.1.2 T
RIPLE
-F
LEX 
R
EAR 
V
IEW
 
 
Figure 4 Triple-Flex Rear View 
 
 
1.  The flue gas vent is 8” diameter and 
exhausts products of combustion.  Refer to 
section 1.7 for installation details. 
2. The rear jacket access panel provides 
access to the combustion air blower for 
servicing. 
3.  The boiler return water connection receives 
cooled water from the system.  This 
connection is a standard ANSI 150# class 3” 
flange. 
12 
 
4.  The drain connection is 1” NPT and provides 
a means for draining water from the boiler.  
For installation details refer to paragraph 
1.4.4.