Bryan Boilers Triple-Flex 150 ユーザーズマニュアル

ページ / 81
 
Date:  
8-4-2010 
 
Revision: 0 
 
Form:  
2396
 
 
NOTE: 
The low fire displacement final adjustment 
should be made at low fire only. 
 
3.  Main gas pressure regulating and shutoff 
valve actuator.  The pressure regulating 
actuator provides slow opening fast closing 
safety shutoff and air/gas ratio control.  The 
actuator controls the pressure difference 
across the gas limiting orifice valve (Figure 7 
item 26) as a function of the pressure 
difference across the furnace section so that 
the air to gas ratio remains constant 
irrespective of air volume changes.  There is 
no need for an upstream constant pressure 
regulator when the supply gas pressure 
does not exceed 56 inches of water column.  
A minimum of 14 inches of water column 
must be supplied at the gas inlet connection 
(Figure 6 item 1).  The supply pressure can 
be measured at the test port (Figure 7 item 
28). 
 
NOTE: 
The supply pressure is not static.  The supply 
pressure is at the maximum full flow of gas 
through the burner. 
 
4.  Manual main gas shutoff valve. 
5.  Pilot ignition transformer. 
6.  Manual pilot gas shutoff valve. 
7.  Pilot gas pressure regulator.  This regulator 
provides a constant gas pressure to the pilot 
when the solenoid valve is energized.  The 
pressure can be adjusted by removing the 
cap and adjusting the slotted screw 
clockwise to increase the pressure and 
counter-clockwise to decrease the pressure.  
The pilot gas supply is taken upstream of 
the main gas cock so the pilot may be 
lighted and adjusted with the main gas cock 
closed. 
8.  Low pilot gas pressure switch (Manual 
Reset) 
9.  Pilot spark igniter assembly.  For further 
detail see Figure 9. 
10.  Pilot gas solenoid valve. 
11. Flame scanner. 
12. Main gas manifold pressure test port (1/4” 
NPT). 
13. Main high gas pressure switch (Manual 
Reset).  This switch should be set 1” of 
water column above the maximum gas 
manifold pressure. 
14. Pilot gas pressure test port (1/4” NPT).  This 
port is also used to record the furnace 
pressure. 
15. Boiler water flow switch.  The boiler water 
flow switch is adjustable within the 
parameters listed in the table. 
   
Mode Of Operation 
Settings 
Switch 
Closed 
Switch 
Open 
Minimum 
30 gpm 
12 gpm 
Maximum 52.1 
gpm 
46.1 
gpm 
Table 4 Water Flow Switch Settings 
 
16. Low Water Cutoff (Manual Reset Probe 
Type). 
17. Combustion air-flow switch.  An airflow 
switch is provided to prove that air is being 
provided to the burners before main flame 
can be established.  The airflow switch can 
be adjusted by turning the screw (Figure 8 
item A) clockwise to increase the pressure 
setting and counter-clockwise to decrease 
the pressure setting.  The switch will open 
on pressure drop.  When the blower is 
running there should be continuity between 
the common and the normally open contacts  
(Figure 8 item B and C).  When the blower is 
interrupted the switch should open and 
cause a safety shutdown.  
 
 
A
B
C
 
Figure 8 Air Flow Switch 
 
18. High burner air pressure switch manual 
reset.  This switch will trip when the air 
pressure in the burner rises above the set-
point, indicating that the burner has become 
plugged with dust or other foreign matter. 
19.  Gas and air mixer assembly. 
14 
 
20. Main 3-phase power connection and fuse