Regency F38-2 Freestanding Gas Heater
7
INSTALLATION
Flueing Requirements 
A100 mm diameter fl ue is required.  For cosmetic 
or aesthetic purposes 6" outer fl ue can be used 
as long as an approved inner fl ue is installed. 
Fasten but do not penetrate the inner sleeve of 
the fl ue when tightening the screw.
The minimum fl ue required is 3.3m from fl oor 
level.
 
Follow all fl ueing manufacturer’s requirements 
and local building codes or AS5601-2004.
GAS CONNECTION
The gas line should be rigid pipe. Copper may 
also be used if approved by AS5601-2004.
The gas connection at the valve is 1/2 male. 
For minimum and maximum supply pressure 
see the System Data Table.
GAS PIPE PRESSURE 
TESTING
The appliance must be isolated from the gas 
supply piping system by closing its individual 
manual shut-off valve during any pressure 
testing of the gas supply piping system at test 
pressures equal to or less than 1/2 psig. (3.45 
kPa).  Disconnect piping from valve at pressures 
over 3.45 kPa (14" w.c.).
The manifold pressure is controlled by a regulator 
built into the gas control, and should be checked 
at the pressure test point.
Note:  To properly check gas pressure, 
both inlet and manifold pressures 
should be checked using the valve 
pressure ports on the valve.
1)  Make sure the valve is in the "OFF" posi-
tion.
2)  Loosen the "IN" (# 7) and/or "OUT" (# 6) 
pressure tap(s), turning counterclockwise 
with a 1/8" wide fl at screwdriver.
3)  Attach manometer to "IN" and/or "OUT" 
pressure tap(s) using a 5/16" ID hose.
4)  Light the pilot and turn the valve to "ON" 
position.
5)  The pressure check should be carried out 
with the unit burning and the setting should 
be within the limits specifi ed on the safety 
label.
6) When fi nished reading manometer, turn 
off the gas valve, disconnect the hose and 
tighten the screw (clockwise) with a 1/8" fl at 
screwdriver. Screw should be snug, but do 
not over tighten.
S.I.T. Valve Description
1)  Gas on/off knob
2)  Manual high/low adjustment
3) Pilot 
Adjustment
4) Thermocouple 
Connection
5) Main 
Operator
6)  Outlet Pressure Tap
7) Inlet 
Pressure 
Tap
8) Pilot 
Outlet
9)  Main Gas Outlet
10) Flange Securing Screw Holes
11) Alternative TC Connection Point
12) Thermoelectric Unit
13) Additional Valve Mounting Hole
F38-NG2: For 0 to 610 meters altitude
F38-LPG2: For 0 to 610 meters altitude
Burner Inlet Orifi ce Sizes:
 
                   NG 
        LPG
 
Burner  
 #33 
       #52 
 
            
Max. Input 
 NG 
38 
mj 
 LPG 
31 
mj
Min. Input 
 NG 
24.1 
mj
 LPG 
24.5 
mj
  
Supply Pressure   
 NG 
1.74 
kPa
 LPG 
2.99 
kPa
Manifold Pressure
 NG 
0.87 
kPa
 LPG 
2.65 
kPa
Electrical: 240 V. 50Hz.
Circulation: High/Off/LO speed fan, 150/89 
CFM.
Log Set: Ceramic fi ber, 7 per set.
Aeration Setting
NG Full 
Open
LPG   6.4 mm
Flue Restrictor Setting
NG Full 
Open
LPG Full 
Open
 
        
System Data
F38-2