12-3
Chapter 12: Parameters
12
12-3 How to set parameters
[1] When the JW-20FL5/20FLT or Z-366J is used
Set parameters of JW-20FL5/20FLT and Z-336J as optional parameters of the control module (CPU
board). Determine the area of the optional parameters using the module No. switch set value of JW-
20FL5/20FLT and Z-336J. The parameters occupy 64 bytes per module.
 How to set the parameters using the JW-14PG
This paragraph describes param-
eter setting procedures (in system
memory) using the hand-held pro-
grammer JW-14PG.
1
 Connect the JW-14PG to the
PG port on the control module
(CPU board.)
2
 Set the PC to program mode.
3
 Set to the initial mode (parameter setting).
4
 Select the option parameter and enter "2" for the module
No. switch number.
5
 Rewrite start switch to 00
(H)
.
Reading parameter address 77
(8)
.
6
 Enter IP address (192.168.250.3) for the parameter address 00 to 03
(8)
.
Decimal notation of parameter 00.
Same as the above, enter the other parameter addresses.
Connection cable
(JW-22KC/24KC)
JW-14PG
Control module (JW-33CUH)
JW-20FL5
(The modules shown below 
are installation examples)
Decimal display of the setting
of parameter 00
JW-14PG screen
 75
HEX
00
 76
HEX
00
I   Parameter  0 - SW: 2
>77
HEX
00
   01
DCM
168
   02
DCM
250
I   Parameter
>03
DCM
003
FL-net module Host PC
Control module
JW-20FL5
JW-20FLT
JW20H
JW-21CU/22CU
JW30H
JW-31CUH1
JW-32CUH1
JW-33CUH1/2/3
FL-net
board
Host J-board
CPU board
Z-336J
Z-300 series Z-311J/312J/313J
Z-500 series Z-511J
- Relationship between the host PC and the con-
trol module
Note: Do not set switch SW3 outside the
range of 0 to 6.
Module No. switch
setting value
Parameter address
(H)
0
00 to 77
1
00 to 77
2
00 to 77
3
00 to 77
4
00 to 77
5
00 to 77
6
00 to 77
← 
Reading a prameter address
(H)
I   Parameter  0 - SW: 2
 I   Parameter
0) I/O
1) Option