Omron C200HE ユーザーズマニュアル

ページ / 564
467
Response Format
@
W
L
x 10
1
x 10
0
x 16
1
x 16
0
FCS
Node no.
End code
Header
code
Terminator
Limitations
Except for the first word of the write data, the write data can be divided into multi-
ple frames.
PC Settings
PC Mode
UM Area
RUN
MONITOR
PROGRAM
Write-protected
Read-protected
---
OK
OK
OK
OK
Execution Conditions
Commands
Responses
Single
Multiple
Single
Multiple
OK
OK
OK
---
End Codes
An end code of 14 (format error) will be returned if the length of the command is
incorrect or the first word of write data isn’t in the first frame.
An end code of 15 (entry number data error) will be returned if the specified write
data exceeds the data area boundary, the beginning word isn’t specified in BCD,
or the write data isn’t hexadecimal. (An end code of A5 will be returned instead of
15 for non-hexadecimal write data in multiple command frames.)
End code
Contents
00
Normal completion
01
Not executable in RUN mode
13
FCS error
14
Format error
15
Entry number data error
18
Frame length error
A3
Aborted due to FCS error in transmit data
A4
Aborted due to format error in transmit data
A5
Aborted due to entry number data error in transmit data
A8
Aborted due to frame length error in transmit data
10-3-11
HR AREA WRITE –– WH
Writes data to the HR area, starting from the specified word. Writing is done word
by word.
Command Format
@      
W
H
FCS
x 10
1
x 10
0
x 10
3
x 10
2
x 10
1
x 10
0
x 16
3
x 16
2
x 16
1
x 16
0
Node no.
Header
code
Beginning word
(0000 to 0099)
Write data 
(for no. of words to write)
Write data (1 word)
Terminator
Response Format
@
W
H
x 10
1
x 10
0
x 16
1
x 16
0
FCS
Node no.
End code
Header
code
Terminator
Host Link Commands
Section 10-3