RuggedCom RX1510 ユーザーズマニュアル

ページ / 45
3. Installation
RuggedCom® RuggedBackbone™
21
RX1510 Installation Guide Rev 104
3.2.3. Chassis Ground Connection
The RX1510 chassis ground connection, shown in 
,
uses a #10-32 screw. It is recommended to terminate the ground connection in a #10 ring lug.
Torque on the chassis ground connection should not exceed 30 in-lbs (3.4 Nm).
Figure 3.11. Chassis Ground Connection
3.2.4. AC Power Supply Wiring
Figure 3.12. Wiring for Single AC Power Supply (HIP module shown)
• For 125/230VAC rated equipment, a appropriately rated AC circuit breaker must be
installed.
• It  is  recommended  to  provide  a  separate  circuit  breaker  for  each  power  supply
module.
• Equipment must be installed according to applicable local wiring codes.