Fujitsu RX600 S5 ユーザーズマニュアル

ページ / 148
RX600 S5
Operating Manual
55
Hardware installation
Connecting the server to the mains
4.4
Connecting the server to the mains
V
CAUTION!
The server is automatically set to a mains voltage in the range 100 - 127 
V / 200 - 240 V. You may only operate the server if its rated voltage range 
corresponds to the local mains voltage.
4.4.1
Installation requirements
The power subsystem consists of:
Power supply modules (PSU)
A power distribution board (PDB)
The power supply subsystem can support up to 4 PSUs which all connect to the 
PDB. The total system is rated 100 - 127 V / 200 - 240 V, 50/60 Hz, 28/14 A.The 
minimum system configuration requires installation of at least two PSUs. The 
PSU is considered hot-swappable(see 
). The system can be configured to support *True AC redundancy or 
non-AC redundancy. 
I
*True AC redundancy is recommended for systems used for critical 
business applications. This will result in the system to continue operation 
during a power failure as the redundant part of the subsystem is plugged 
into a separate AC source [e.g. uninterruptable power supply (UPS)).
I
Refer to tables below for maximum DC loading for both AC redundant 
and AC non redundant configurations.
Installation requirements for AC redundant configurations
The AC redundant configuration is with two PSU plugged into a main AC source 
and two other PSUs plugged into a separate AC source (e.g. UPS).
PSU Configuration
Max. DC Loading
DC Redundancy
1+1 (2 PSUs) 
830W 
Yes 
2+2 (4 PSUs)
1580W
Yes
Table 2: Maximum DC Loading Requirements