Fujitsu RX600 S5 ユーザーズマニュアル

ページ / 148
RX600 S5
Operating Manual
57
Hardware installation
Connecting the server to the mains
AC source related power supply configuration and system load limits
The system configuration and load is limited by the number of AC mains power 
sources available as indicated in the following table.
Installation in PRIMECENTER/Datacenter rack
Please follow the installation requirements for connection to the mains 
described in the rack manuals.
Number 
of power 
supply 
modules 
installed 
AC redundant systems 
(requires 2 AC sources)
AC non-redundant systems 
(connected to 1 AC source) 
Max. DC 
loading to 
support AC 
redundancy
Installation 
requirements
Max. DC 
loading for AC 
non-redundant 
systems
Installation 
requirements 
2 830W
PSUs 
connected to 
mains (1+1) 
1580W
2 PSUs 
connected to 
mains (1+1) 
3
N/A
N/A
2320W
3 PSUs 
connected to 
mains (2+1) 
4
1580W
2 PSUs 
connected to 
mains
2 PSUs 
connected to 
an isolated AC 
source 
e.g. UPS (2+2)
2320W
4 PSUs 
connected to 
mains (3+1) 
Table 4: System power supply configuration and system load limits